Lenovo System x3550 M4 Installation And Service Manual page 423

Hide thumbs Also See for System x3550 M4:
Table of Contents

Advertisement

11
CIM Information
Prefix: PLAT ID: 0522
User Response
1. Make sure that there are no obstructions, such as bundled cables, to the airflow from the
power-supply fan.
2. Replace power supply n. (n = power supply number)
• 80070204-0a02ffff : Sensor [SensorElementName] has transitioned to critical from a less severe
state. (PS 2 Fan Fault)
This message is for the use case when an implementation has detected a Sensor transitioned to critical
from less severe.
May also be shown as 800702040a02ffff or 0x800702040a02ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Fan Failure
SNMP Trap ID
11
CIM Information
Prefix: PLAT ID: 0522
User Response
1. Make sure that there are no obstructions, such as bundled cables, to the airflow from the
power-supply fan.
2. Replace power supply n. (n = power supply number)
• 80070208-0a01ffff : Sensor [SensorElementName] has transitioned to critical from a less severe
state. (PS 1 Therm Fault)
This message is for the use case when an implementation has detected a Sensor transitioned to critical
from less severe.
May also be shown as 800702080a01ffff or 0x800702080a01ffff
Severity
Error
Appendix A. Integrated management module II (IMM2) error messages
409