Lenovo System x3550 M4 Installation And Service Manual page 409

Hide thumbs Also See for System x3550 M4:
Table of Contents

Advertisement

3. Check the server airflow. Make sure that nothing is blocking the air from coming into or
preventing the air from exiting the server.
• 80010901-2c01ffff : Numeric sensor [NumericSensorElementName] going high (upper critical) has
asserted. (Mezz Card Temp)
This message is for the use case when an implementation has detected an Upper Critical sensor going
high has asserted.
May also be shown as 800109012c01ffff or 0x800109012c01ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Temperature
SNMP Trap ID
0
CIM Information
Prefix: PLAT ID: 0494
User Response
1. Reduce the ambient temperature.
2. Ensure the air baffle is installed correctly.
3. Check the server airflow. Make sure that nothing is blocking the air from coming into or
preventing the air from exiting the server.
80010901-2d01ffff : Numeric sensor [NumericSensorElementName] going high (upper critical)
has asserted. (PCH Temp)
This message is for the use case when an implementation has detected an Upper Critical sensor going
high has asserted.
May also be shown as 800109012d01ffff or 0x800109012d01ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Appendix A. Integrated management module II (IMM2) error messages
395