Product Specifications

LAN
Ethernet
Protection
Protocols
Analog Input
Type
Resolution
Sampling Rate
I/O Mode
Input Range
Accuracy
Built-in Resistor for Current
Input
Input Impedance
Analog Output
Resolution
Output Range
Voltage Output
Accuracy
Load Resistor
RTD
Input Type
Sampling Rate
Resolution
Accuracy
Input Impedance
Thermocouple Input
Sensor Type
Fault and Overvoltage
protection
Sampling Rate
Resolution
Accuracy
Input Impedance
Digital Input
Sensor Type
I/O Mode
Dry Contact
2 x 10/100 Mbps switch ports, RJ45
1.5 KV magnetic isolation
Modbus/TCP, OPC Server, TCP/IP, UDP, DHCP, Bootp, HTTP
Differential input
16 bits
12 samples per second (all channels)
Voltage or Current
0 to 10 VDC, 4 to 20 mA
±0.1% FSR @ 25°C; ±0.3% FSR @ -10 and 60°C
120 ohms
10M ohms
12 bits
0 to 10 VDC, 4 to 20 mA
10 mA (Max.)
±0.1% FSR @ 25°C; ±0.3% FSR @ -10 and 60°C
Internal power: 400 ohms; External 24V power: 1000 ohms
PT50, PT100, PT200, PT500, PT1000; Resistance of 10 ohms,
20 ohms, and 100 ohms
12 samples per second (all channels)
16 bits
±0.1% FSR @ 25°C; ±0.3% FSR @ -10 and 60°C
625K ohms
J, K, T, E, R, S, B, N; Mili Volt Type: ±78.126 mV, ±39.062 mV,
and ±19.532 mV
±35 VDC (power off); -25 VDC to +30 VDC (power on)
12 samples per second (all channels)
16 bits
±0.1% FSR @ 25°C; ±0.3% FSR @ -10 and 60°C
10M ohms
NPN, PNP, and Dry contact
DI or Event Counter
Logic 0: short to GND; Logic 1: open