E1212 Modbus Mapping - Moxa Technologies ioLogik E1210 User Manual

Hide thumbs Also See for ioLogik E1210:
Table of Contents

Advertisement

ioLogik E1200 User's Manual

E1212 Modbus Mapping

0xxxx Read/Write Coils (Functions 1, 5, 15)
Reference
DO Channel
00001
00002
00003
00004
00005
00006
00007
00008
00017
00018
00019
00020
00021
00022
00023
00024
DI Channel
00257
00258
00259
00260
00261
00262
00263
00264
00265
00266
00267
00268
00269
00270
00271
00272
00273
00274
00275
Address
Data Type Description
0x0000
1 bit
0x0001
1 bit
0x0002
1 bit
0x0003
1 bit
0x0004
1 bit
0x0005
1 bit
0x0006
1 bit
0x0007
1 bit
0x0010
1 bit
0x0011
1 bit
0x0012
1 bit
0x0013
1 bit
0x0014
1 bit
0x0015
1 bit
0x0016
1 bit
0x0017
1 bit
0x0100
1 bit
0x0101
1 bit
0x0102
1 bit
0x0103
1 bit
0x0104
1 bit
0x0105
1 bit
0x0106
1 bit
0x0107
1 bit
0x0108
1 bit
0x0109
1 bit
0x010A
1 bit
0x010B
1 bit
0x010C
1 bit
0x010D
1 bit
0x010E
1 bit
0x010F
1 bit
0x0110
1 bit
0x0111
1 bit
0x0112
1 bit
Modbus/TCP Address Mappings
CH0 DO Value 0: Off 1: On
CH1 DO Value 0: Off 1: On
CH2 DO Value 0: Off 1: On
CH3 DO Value 0: Off 1: On
CH4 DO Value 0: Off 1: On
CH5 DO Value 0: Off 1: On
CH6 DO Value 0: Off 1: On
CH7 DO Value 0: Off 1: On
CH0 DO Pulse Operate Status 0: Off 1: On
CH1 DO Pulse Operate Status 0: Off 1: On
CH2 DO Pulse Operate Status 0: Off 1: On
CH3 DO Pulse Operate Status 0: Off 1: On
CH4 DO Pulse Operate Status 0: Off 1: On
CH5 DO Pulse Operate Status 0: Off 1: On
CH6 DO Pulse Operate Status 0: Off 1: On
CH7 DO Pulse Operate Status 0: Off 1: On
CH0 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH1 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH2 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH3 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH4 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH5 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH6 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH7 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH8 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH9 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH10 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH11 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH12 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH13 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH14 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH15 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH0 DI Clear Count Value
Read
Always return:0
Write:
1 : Clear counter value
0 : Return illegal data value(0x03)
CH1 DI Clear Count Value
Read
Always return:0
Write:
1 : Clear counter value
0 : Return illegal data value(0x03)
CH2 DI Clear Count Value
Read
Always return:0
Write:
1 : Clear counter value
A-5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents