ioLogik E1200 Series User's Manual
Wet Contact
Isolation
Counter/Frequency
Digital Output
I/O Mode
Pulse Wave Width/Frequency 1 ms/500 Hz
Over-voltage Protection
Over-current Limit
Over-temperature Shutdown
Output Current Rating
Isolation
Relay Output
Type:
Contact Rating
Inductance Load
Resistance Load
Breakdown Voltage
Relay On/Off Time
Initial Insulation Resistance
Expected Life
Initial Contact Resistance
Pulse Output
Environmental Limits
Operating Temperature
Storage Temperature
Ambient Relative Humidity
Power Requirement
Power Input
Power Consumption
Mechanical Specifications
Wiring
Dimensions
Regulatory Approvals
EMI
EMS
Shock
Freefall
Vibration
Agency Approvals
EMC
Logic 0: 0 to 3 VDC; Logic 1: 10 to 30 VDC (DI COM to DI)
3K VDC or 2K Vrms
250 Hz, power off storage
DO or Pulse Output (up to 500 Hz)
45 VDC
600 mA per channel
175°C (typical), 150°C (min.)
Max. 200 mA per channel
3K VDC or 2K Vrms
Form A (N.O.) relay outputs, 5 A
5 A @ 30 VDC, 5 A @ 250 VAC, 5 A @ 110 VAC
2 A
5 A
500 VAC
10 ms (Max.)
1G min. @ 500 VDC
100,000 times (Typical)
100 milli-ohms (Max.)
0.3 Hz at rated load
-10 to 60°C (14 to 140°F)
-40 to 85°C (-40 to 185°F)
5 to 95% (non-condensing)
24 VDC nominal, 12 to 36 VDC
130 mA @ 24 VDC (typical)
I/O cable, 14 AWG Max.
27 x 132 x 84 mm
FCC Part 15, CISPR (EN55022) class A
IEC 61000-4, IEC 61000-6
IEC60068-2-27
IEC60068-2-32
IEC60068-2-6
FCC Part 15, CISPR (EN55022) Class A
CE: IEC 61000-4-2 (ESD), Level 2/3
1-6
Introduction

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents