Download Print this page
Moxa Technologies ioLogik E1510-T Quick Installation Manual
Moxa Technologies ioLogik E1510-T Quick Installation Manual

Moxa Technologies ioLogik E1510-T Quick Installation Manual

Iologik e1500 series

Advertisement

Quick Links

ioLogik E1500 Series

Quick Installation Guide

Second Edition, February 2015
Overview
With a threaded M12 Ethernet port to ensure wired connectivity, a
spring-type terminal block for vibration-resistant cabling, and a
DIN rail mount assembly, the ioLogik E1500 series is designed to
withstand the severe vibrations experienced with rolling stock and
wayside applications. Carefully engineered channel-to-channel
isolation gives protection against cross-line power surges and
crosstalk, ensuring stable data communications. In addition, the
ioLogik E1500 is compliant with EN 50121-3-2, EN 50121-4, and
essential sections of the EN 50155 standard (covering operating
temperature, power input voltage, electrical surges, ESD, and
vibration), all of which are required for electronic equipment used
on or around railway vehicles.
Model Selection
ioLogik
DI
DO
DIO
Relay
AI
E1510-T
12
E1512-T
4
4
Package Checklist
1 ioLogik E1500 series remote I/O product
Documentation and software CD
Quick installation guide (printed)
P/N: 1802015000011
– 1 –

Specifications

System
Ethernet
Protection
Protocols
Power Input
Wiring
Dimensions
Weight
Operating Temperature -40 to 85°C (-40 to 185°F)
Storage Temperature
Ambient Relative
Humidity
Altitude:
Note: Please contact Moxa if you require products guaranteed to
function properly at higher altitudes.
Standards and
Certifications
Warranty Period
Details
Digital Input
Sensor Type
I/O Mode
Dry Contact
AO
RTD TC
Wet Contact
Isolation
Counter/Frequency
Digital Output
I/O Mode
Pulse Wave
Width/Frequency
Over-voltage
Protection
Over-current Protection 2.6 A (4 channels @ 650 mA)
Over-temperature
Shutdown
Current Rating
Isolation
10/100 Mbps, M12 connector
1.5 KV magnetic isolation
Modbus/TCP, TCP/IP, UDP, DHCP, Bootp,
HTTP
24 VDC nominal, 12 to 48 VDC
I/O cable, max. 14 AWG
144 x 124 x 30 mm (5.67 x 4.88 x 1.18 in)
825 g
-40 to 85°C (-40 to 185°F)
5 to 95% (non-condensing)
Up to 2000 m
UL 508, EN 50155, EN 50121-3-2, EN
50121-4
5 years
See www.moxa.com/warranty
NPN, PNP, and Dry contact
DI or Event Counter
• On: short to GND
• Off: open
• On: 0 to 3 VDC
• Off: 10 to 30 VDC
3k VDC or 2k Vrms
250 Hz, power off storage
DO or Pulse Output
1 ms/500 Hz
45 VDC
175°C (typical), 150°C (min.)
200 mA per channel
3k VDC or 2k Vrms
– 2 –
Installation
Power and Networking
Connect the +12 to +48 VDC power line to the ioLogik E1500's
terminal block V+ terminal, and connect the ground from the
power supply to the V- terminal. If an earth ground is available,
connect the ground pin (
).
Mounting and Cabling
The ioLogik E1500 can be used with both DIN rail and wall mounts.
When mounting on a DIN rail, release the bottom mounting kit,
install the ioLogik on the rail, and then restore the bottom
mounting kit to fix the ioLogik to the rail. When using wall
mounting, release both the upper and bottom DIN rail kits.
The ioLogik E1500 has an M12 Ethernet port for connecting either
a standard direct-Ethernet or crossover-Ethernet cable via a
locking M12 connector.
LED Indicators
Type
Color
Description
PWR
Green
System power in ON
Off
System power is OFF
RDY
Green
System is ready
Green Blinking Located
Red
System Booting-up Error
Green/Red
Safe Mode
Blinking
Red Blinking
Firmware upgrade (LED flashes for 3
seconds then stays red until restart)
Off
System is not ready
LAN
Green
100 Mbps
Amber
10 Mbps
Blinking
Data Transmitting
Off
Ethernet Off
EXP
Green
Expansion Mode Ready
Red
Configuration Failure
Off
Stand-alone Mode
DI
Green
Channel ON
Off
Channel OFF
DIO
Green
Channel ON
Off
Channel OFF
– 3 –

Advertisement

loading

Summary of Contents for Moxa Technologies ioLogik E1510-T

  • Page 1: Specifications

    Specifications Installation System Power and Networking ioLogik E1500 Series Ethernet 10/100 Mbps, M12 connector Protection 1.5 KV magnetic isolation Connect the +12 to +48 VDC power line to the ioLogik E1500’s Quick Installation Guide Protocols Modbus/TCP, TCP/IP, UDP, DHCP, Bootp, terminal block V+ terminal, and connect the ground from the HTTP power supply to the V- terminal.
  • Page 2: System Configuration

    I/O Wiring DIO_DI wet contact mode (no CH-CH isolation) Load Factory Default Settings DI dry contact mode There are three ways to restore the ioLogik E1500 to the factory default settings. 1. Remove the two screws and the aluminum plate, and then press and hold the RESET button for 5 seconds.

This manual is also suitable for:

Iologik e1512-t