ioLogik E1210
Digital Input
Sensor Type: NPN, PNP, and Dry contact
I/O Mode: DI or Event Counter
Dry Contact:
• Logic 0: short to GND
• Logic 1: open
Wet Contact:
• Logic 0: 0 to 3 VDC
• Logic 1: 10 to 30 VDC (DI COM to DI)
Isolation: 3K VDC or 2K Vrms
Counter/Frequency: 250 Hz, power off storage
Power Requirements
Power Consumption: 111 mA @ 24 VDC
MTBF
(meantime between failures)
Time: 671,345 hrs
Database: Telcordia (Bellcore)
ioLogik E1211
Digital Output
I/O Mode: DO or Pulse Output
Pulse Wave Width/Frequency: 1 ms/500 Hz
Over-voltage Protection: 45 VDC
Over-current Protection: 2.6 A (4 channels @ 650 mA)
Over-temperature Shutdown: 175°C (typical), 150°C (min.)
Current Rating: 200 mA per channel
Isolation: 3K VDC or 2K Vrms
Power Requirements
Power Consumption: 208 mA @ 24 VDC
MTBF
(meantime between failures)
Time: 221,662 hrs
Database: Telcordia (Bellcore)
ioLogik E1212
Digital Input
Sensor Type: NPN, PNP, and Dry contact
I/O Mode: DI or Event Counter
Dry Contact:
• Logic 0: short to GND
• Logic 1: open
Wet Contact:
• Logic 0: 0 to 3 VDC
• Logic 1: 10 to 30 VDC (DI COM to DI)
Isolation: 3K VDC or 2K Vrms
Counter/Frequency: 250 Hz, power off storage