DO Channels

On the DO Channels page, configure each DO (digital output) channel by clicking on the channel.
DO Channels can operate in DO mode or Pulse Output mode. In DO mode, output is either on or off.
In Pulse Output mode, a configurable square wave is generated.
The Power On Setting field is used to specify the channel's configuration when the ioLogik E1200
is powered on, and the Safe Status Setting field specifies the channel's configuration when the
ioLogik E1200 enters Safe Mode. Note that Safe Status is controlled by the Connection Watchdog,
which is disabled by default. If the Connection Watchdog is disabled, the ioLogik E1200 will never
enter Safe Mode and your Safe Status settings will have no effect.
Users may also configure the alias name and the logic definition on this page.
ATTENTION
Remove the screw on the back panel and open the cover to configure the jumpers for input or
output selection of the DIO channels. Refer to chapter 2 for detailed jumper settings.