Terminal Arrangement Of The Main Circuit Terminal, Power Supply And The Motor Wiring - Mitsubishi Electric FR-E700 Instruction Manual

Fr-e740-016 to 300 - ec; fr-e720s-008 to 110 - ec
Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

Main circuit terminal specifications
2.2.2
Terminal arrangement of the main circuit terminal, power supply and the motor
wiring
Three-phase 400V class
FR-E740-016 to 095
Jumper
-
+
R/L1 S/L2 T/L3
PR
Power supply
FR-E740-230, 300
-
+
PR R/L1 S/L2 T/L3
Jumper
(230: M4/300: M5)
Power supply
Single-phase 200V class
FR-E720S-008 to 030
Screw size (M3.5)
-
L1
N
Screw size
Power supply
NOTE
Make sure the power cables are connected to the R/L1, S/L2, T/L3. (Phase need not be matched.) Never connect the
power cable to the U, V, W of the inverter. Doing so will damage the inverter.
Connect the motor to U, V, W. Turning ON the forward rotation switch (signal) at this time rotates the motor
counterclockwise when viewed from the load shaft.
16
Screw size (M4)
IM
Screw size
(M4)
Motor
Screw size (230: M4/300: M5)
Screw size
IM
Motor
Jumper
+
PR
IM
(M3.5)
Motor
FR-E740-120, 170
Screw size (M4)
Jumper
R/L1 S/L2 T/L3
-
+ PR
Power supply
FR-E720S-050 to 110
Jumper
-
+
Screw size (M4)
L1 N
PR
Power supply
Screw size
(M4)
IM
Motor
IM
Screw size
(M4)
Motor

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-e740ec

Table of Contents