Special operation and frequency control
(4)
I/O signals and parameter setting
Set "40 to 43" in Pr. 128 to perform dancer control.
Set "14" in any of Pr. 178 to Pr. 184 (input terminal function selection) to assign PID control selection signal (X14) to turn the
X14 signal ON.
When the X14 signal is not assigned, only the Pr. 128 setting makes dancer control valid.
Input the main speed command (External, PU, Network). The main speed command in any operation mode can be input.
(Note that terminal 4 can not be used as the main speed command.)
Input the set point using Pr. 133, then input the measured value signal (dancer roller position detection signal) across
terminal 4 and 5 of the inverter.
REMARKS
When Pr. 128 = "0" or X14 signal is OFF, normal inverter operation is performed without dancer control.
Turning ON/OFF of bit of the terminal, to which X14 signal is assigned through network as RS-485 communication, enables
dancer control.
Signal
Terminal Used
Depending
on
X14
Pr. 178 to Pr. 184
4
4
FUP
FDN
Depending
on
Pr. 190 to Pr. 192
RL
PID
SE
SE
∗1
When the X14 signal is not assigned, only the Pr. 128 setting makes dancer control valid.
∗2
The shaded area indicates the parameter initial value.
∗3
When 100 or larger value is set in any of Pr. 190 to Pr. 192 (output terminal function selection), the terminal output has negative logic. (For details, Refer to page 136)
NOTE
Changing the terminal function using any of Pr. 178 to Pr. 184 and Pr.190 to Pr.192 may affect the other functions. Make
setting after confirming the function of each terminal.
When the Pr. 267 setting was changed, check the voltage/current input switch setting. Different setting may cause a
fault, failure or malfunction. (Refer to page 167 for setting)
242
Function
PID control
Turn ON X14 signal to perform dancer
control. ∗1
selection
Input the signal from the dancer roller
detector (measured value signal).
Measured value
4 to 20mA.....0 to 100%
input
0 to 5V..........0 to 100%
0 to 10V........0 to 100%
Output to indicate that the measured
value signal exceeded the maximum
Upper limit output
value
(Pr. 131).
Output when the measured value signal
Lower limit output
falls below the minimum value (Pr. 132).
Output
Forward (reverse)
indication of the parameter unit is
rotation direction
forward rotation (FWD) and "OFF" when
output
reverse rotation (REV) or stop (STOP).
During PID control
Turns ON during PID control.
activated
Output terminal
Common terminal for open collector
common
output terminal.
Description
is
"ON"
when
the
output
Parameter Setting
Set 14 in any of Pr. 178 to Pr. 184.
Pr.128 = 40, 41, 42, 43
Pr.267 = 0 ∗2
Pr.267 = 1
Pr.267 = 2
Pr.128 = 40, 41, 42, 43
Pr.131 ≠ 9999
Set 15 or 115 in any of Pr. 190 to Pr. 192.
∗3
Pr.128 = 40, 41, 42, 43
Pr.132 ≠ 9999
Set 14 or 114 in any of Pr. 190 to Pr. 192.
∗3
Set 16 or 116 in any of Pr. 190 to Pr. 192.
∗3
Set 47 or 147 in any of Pr. 190 to Pr. 192.
∗3