6.1.5

Checking the inverter and converter modules

<Preparation>
(1) Disconnect the external power supply cables (R/L1, S/L2, T/L3) and motor cables (U, V, W).
(2) Prepare a tester. (Use 100Ω range.)
<Checking method>
Change the polarity of the tester alternately at the inverter terminals R/L1, S/L2, T/L3, U, V, W, + and -, and check for
continuity.
NOTE
1. Before measurement, check that the smoothing capacitor is discharged.
2. At the time of discontinuity, the measured value is almost
smoothing capacitor, the tester may not indicate
several tens-of ohms depending on the module type, circuit tester type, etc. If all measured values are almost the
same, the modules are without fault.
<Module device numbers and terminals to be checked>
Tester Polarity
Measured
+
R/L1
Discontinuity
D1
+
R/L1 Continuity
+
S/L2
Discontinuity
D2
+
S/L2 Continuity
+
T/L3∗
Discontinuity
D3∗
+
T/L3∗ Continuity
+
U
Discontinuity
TR1
+
U
Continuity
+
V
Discontinuity
TR3
+
V
Continuity
+
W
Discontinuity
TR5
+
W
Continuity
(Assumes the use of an analog meter.)
* T/L3, D3 and D6 are only for the three-phase power input specification models.
Tester Polarity
Value
R/L1
D4
R/L1 Discontinuity
S/L2
D5
S/L2 Discontinuity
T/L3∗
D6∗
T/L3∗ Discontinuity
U
TR4
U
V
TR6
V
W
TR2
W
. When there is an instantaneous continuity, due to the
. At the time of continuity, the measured value is several to
Measured
Value
Converter module
Continuity
D1
D2
Continuity
R/L1
Continuity
S/L2
Continuity
T/L3
Discontinuity
Continuity
Discontinuity
D4
D5
Continuity
Discontinuity
Inspection items
+
Inverter module
TR1
TR3
D3
C
D6
TR4
TR6
TR5
U
V
W
TR2
6