Useful functions
(1)
Life alarm display and signal output (Y90 signal, Pr. 255)
Whether any of the control circuit capacitor, main circuit capacitor, cooling fan and inrush current limit circuit has reached
the life alarm output level or not can be checked by Pr. 255 Life alarm status display and life alarm signal (Y90).
bit
15
7
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0
Pr. 255
Bit
(decimal)
(binary)
15
1111
14
1110
13
1101
12
1100
11
1011
10
1010
9
1001
8
1000
7
0111
6
0110
5
0101
4
0100
3
0011
2
0010
1
0001
0
0000
The life alarm signal (Y90) turns ON when any of the control circuit capacitor, main circuit capacitor, cooling fan and inrush
current limit circuit reaches the life alarm output level.
For the terminal used for the Y90 signal, set "90" (positive logic) or "190" (negative logic) to any of Pr. 190 to Pr. 192 (output
terminal function selection).
NOTE
Changing the terminal assignment using Pr. 190 to Pr. 192 (output terminal function selection) may affect the other
functions. Make setting after confirming the function of each terminal.
(2)
Inrush current limit circuit life display (Pr. 256)
The life of the inrush current limit circuit (relay, contactor and inrush resistor) is displayed in Pr. 256 .
The number of contact (relay, contactor, thyristor) ON times is counted, and it is counted down from 100% (0 times) every
1%/10,000 times.
As soon as 10% (900,000 times) is reached, Pr. 255 bit 3 is turned ON and also an alarm is output to the Y90 signal.
(3)
Control circuit capacitor life display (Pr. 257)
The deterioration degree of the control circuit capacitor is displayed in Pr. 257 as a life.
In the operating status, the control circuit capacitor life is calculated from the energization time and temperature, and is
counted down from 100%.
As soon as the control circuit capacitor life falls below 10%, Pr. 255 bit 0 is turned ON and also an alarm is output to the
Y90 signal.
250
0
1
bit0 Control circuit capacitor life
bit1 Main circuit capacitor life
bit2 Cooling fan life
bit3 Inrush current limit circuit life
Inrush Current
Cooling
Suppression
Fan Life
Circuit Life
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
Pr. 255 read
Main Circuit
Control Circuit
Capacitor Life
Capacitor Life
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
: With warnings, ×: Without warnings
Pr. 255 setting read
Bit image is displayed
in decimal