Special operation and frequency control
4)Reverse operation
Increases the manipulated variable (output frequency) if deviation X = (set point - measured value) is positive, and
decreases the manipulated variable if deviation is negative.
Set point
5)Forward action
Increases the manipulated variable (output frequency) if deviation X = (set point - measured value) is negative, and
decreases the manipulated variable if deviation is positive.
Set point
Relationships between deviation and manipulated variable (output frequency)
Positive
Reverse action
Forward action
(3)
Connection diagram
Source logic
Pr. 128 = 20
Pr. 183 = 14
Pr. 190 = 15
Pr. 191 = 14
Pr. 192 = 16
∗1
The power supply must be selected in accordance with the power specifications of the detector used.
∗2
The used output signal terminal changes depending on the Pr. 190 to Pr. 192 (output terminal selection) setting.
∗3
The used input signal terminal changes depending on the Pr. 178 to Pr. 184 (input terminal selection) setting.
∗4
The AU signal need not be input.
234
[Heating]
+
X>0
X<0
-
Feedback signal
(measured value)
[Cooling]
+
X>0
X<0
-
Feedback signal
(measured value)
Deviation
Negative
MCCB
Power supply
Forward rotation
Reverse rotation
PID control selection
Setting Potentiometer
(Set point setting)
AC1φ
200/220V 50/60Hz
Cold
Increase
Hot
Decrease
Decrease
Too cold
Increase
Hot
Deviation
Inverter
R/L1
U
S/L2
V
W
T/L3
STF
STR
MRS(X14)
*3
PC
(FUP)RUN
Upper limit
*2
(FDN)FU
Lower limit
*2
10
2
5
SE
Output signal
common
4
*4
(measured value) 4 to 20mA
0
24V
Power
*1
supply
Deviation
Set point
Measured value
Measured value
Set point
Pump
Motor
IM
P
2-wire type
3-wire type
Detector
-
+
+
-
+
(OUT)
(COM)
(24V)