Mitsubishi Electric FR-E700 Instruction Manual page 176

Fr-e740-016 to 300 - ec; fr-e720s-008 to 110 - ec
Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

(b) Method to adjust any point without application of a voltage (current) to across terminals 2-5 (4-5)
(To change from 4V (80%) to 5V (100%))
Operation
1.
Confirm the RUN indication and operation mode
indication
The inverter should be at a stop.
The inverter should be in the PU operation mode.
(Use
)
2.
Press
to choose the parameter setting
mode.
3.
Turn
until
appears.
4.
Press
until
appears.
5.
Turn
until
(
Set to C4 Terminal 2 frequency setting gain.
6.
Press
to display the analog voltage
(current) value (%).
7.
Turn
to set gain voltage (%).
"0V(0mA) is 0%, 10V(5V, 20mA) is 100%"
REMARKS
The current setting at the instant of turning
displayed.
You can not check after performing operation in step 7.
8.
Press
to set.
Turn
to read another parameter.
Press
to return to the
Press
twice to show the next parameter (
REMARKS
By pressing
You can not check after performing operation in step 7.
Frequency setting by analog input (terminal 2, 4)
) appears.
Flicker...Parameter setting complete!!
indication (step 4).
after step 6, you can confirm the current frequency setting bias/gain setting.
Display
PRM indication is lit.
(The parameter number read previously appears.)
C1 to C7 setting
is enabled.
Terminal 2 input is
Terminal 4 input
selected
is selected
Analog voltage (current) value (%)
across terminals 2-5 (across
terminals 4-5)
The gain frequency is reached
when the analog voltage (current)
value across terminals 2-5 (across
terminals 4-5) is 100%.
is
A
Terminal 2 input
is selected
(Adjustment completed)
).
Terminal 4 input
is selected
4
173