REMARKS
⋅ The priorities of the frequency commands by the external signals are "jog operation > multi-speed operation > terminal 4 analog
input > terminal 2 analog input". (Refer to page 143 for the frequency command by analog input)
⋅ Valid in external operation mode or PU/external combined operation mode (Pr. 79 = "3" or "4").
⋅ Multi-speed parameters can also be set in the PU or external operation mode.
⋅ Pr. 24 to Pr. 27 and Pr. 232 to Pr. 239 settings have no priority between them.
⋅ When a value other than "0" is set in Pr. 59 Remote function selection, the RH, RM and RL signals are used as the remote setting
signals and the multi-speed setting becomes invalid.
⋅ When making analog input compensation, set "1" in Pr. 28 Multi-speed input compensation selection.
CAUTION
⋅ The RH, RM, RL, REX signals can be assigned to the input terminal using any of Pr. 178 to Pr. 189 (input terminal function
selection). When terminal assignment is changed, the other functions may be affected. Please make setting after confirming the
function of each terminal.
♦ Parameters referred to ♦
Pr. 1 Maximum frequency, Pr. 2 Minimum frequency
Pr. 15 Jog frequency
Refer to page 86
Pr. 28 Multi-speed input compensation selection
Pr. 59 Remote function selection
Pr. 178 to Pr. 189 (input terminal function selection)
Refer to page 78
Refer to page 88
Refer to page 89
Refer to page 101
Frequency setting by external terminals