Mitsubishi Electric F700 Instruction Manual page 157

Fr-f720-0.75k to 110k; fr-f740-0.75k to 560k
Hide thumbs Also See for F700:
Table of Contents

Advertisement

60Hz
Bias
C2
(Pr. 902)
0
0
Frequency setting signal
0
C3 (Pr. 902)
60Hz
Bias
C5
(Pr. 904)
0
20
0
4
Frequency setting signal
C6 (Pr. 904)
CAUTION
⋅ When the terminal 2 is calibrated to change the inclination of the set frequency, the setting of the terminal 1 is also changed.
⋅ When a voltage is input to the terminal 1 to make calibration, (terminal 2 (4) analog value + terminal 1 analog value) is the analog
calibration value.
⋅ When the voltage/current input specifications were changed using Pr. 73 and Pr. 267, be sure to make calibration.
(3) Analog input display unit changing (Pr. 241)
⋅ You can change the analog input display unit (%/V/mA) for analog input bias/gain calibration.
⋅ Depending on the terminal input specification set to Pr. 73 and Pr. 267, the display units of C3 (Pr. 902), C4 (Pr. 903), C6 (Pr.
904) C7 (Pr. 905) change as shown below.
Analog Command
(terminal 2, 4)
(according to Pr. 73, Pr. 267 )
0 to 5V input
0 to 10V input
4 to 20mA input
REMARKS
⋅ Analog input display is not displayed correctly if voltage is applied to terminal 1 when terminal 1 input specifications (0 to ±5V, 0
to ±10V) and main speed (terminal 2, terminal 4 input) specifications (0 to 5V, 0 to 10V, 0 to 20mA) differ. (For example, 5V
(100%) is analog displayed when 0V and 10V are applied to terminal 2 and terminal 1 respectively in the initial status.
⋅ Set "0" (initial value is 0% display) in Pr. 241 to use.
Initial value
Pr.125
Gain
100%
5V
10V
C4 (Pr. 903)
Initial value
Pr. 126
Gain
100%
20mA
C7 (Pr. 905)
Pr. 241 = 0 (initial value)
0 to 5V → displayed in 0 to 100%(0.1%).
0 to 10V → displayed in 0 to 100%(0.1%).
0 to 20mA → displayed in 0 to 100%(0.1%).
Frequency setting by analog input (terminal 1, 2, 4)
(1) Change
the
frequency
analog input. (Pr. 125, Pr. 126)
⋅ Set a value in Pr. 125 (Pr. 126) when changing only
the frequency setting (gain) of the maximum analog
input power (current). (C2 (Pr. 902) to C7 (Pr. 905)
setting need not be changed)
(2) Analog input bias/gain calibration (C2(Pr.
902) to C7(Pr. 905), )
⋅ The "bias" and "gain" functions are used to adjust the
relationship between the input signal entered from
outside the inverter to set the output frequency, e.g. 0
to 5V, 0 to 10V or 0 to 20mADC, and the output
frequency.
⋅ Set the bias frequency of the terminal 2 input using
C2 (Pr. 902). (initial set to the frequency at 0V)
⋅ Using Pr. 125, set the output frequency relative to the
frequency command voltage (current) set in Pr. 73
Analog input selection.
⋅ Set the bias frequency of the terminal 4 input using
C5 (Pr. 904). (initial set to the frequency at 4mA)
⋅ Using Pr. 126, set the output frequency relative to
20mA of the frequency command current (0 to
20mA).
⋅ There are three methods to adjust the frequency
setting voltage (current) bias/gain.
(a) Method to adjust any point by application of
voltage (current) to across the terminals 2-5 (4-5).
page 150
(b) Method to adjust any point without application of a
voltage (current) to across terminals 2-5(4-5).
page 151
(c) Adjusting only the frequency without adjusting the
voltage (current).
0 to 100% → displayed in 0 to 5V(0.01V).
0 to 100% → displayed in 0 to 10V(0.01V).
0 to 100% → displayed in 0 to 20mA(0.01mA).
at
maximum
page 152
Pr. 241 = 1
149
4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents