Mitsubishi Electric F700 Instruction Manual page 95

Fr-f720-0.75k to 110k; fr-f740-0.75k to 560k
Hide thumbs Also See for F700:
Table of Contents

Advertisement

(2) Jog operation from PU
⋅ Set the PU (FR-DU07/FR-PU04/FR-PU07) to the jog operation mode. Operation is performed only while the start button is pressed.
1.
Confirmation of the RUN indication and
operation mode indication
The monitor mode should have been selected.
The inverter should be at a stop.
2.
Press
PU JOG operation mode.
3.
Press
While
motor rotates.
Rotates at 5Hz. (initial value of Pr. 15)
4.
Release
[When changing the frequency of PU JOG
operation]
5.
Press
setting mode.
6.
Turn
appears.
7.
Press
value. (5Hz)
8.
Turn
"
9.
Press
10.
Perform the operations in steps 1 to 4.
The motor rotates at 10Hz.
CAUTION
⋅ When Pr. 29 Acceleration/deceleration pattern selection = "1" (S-pattern acceleration/deceleration A), the acceleration/
deceleration time is the period of time required to reach Pr. 3 Base frequency.
⋅ The Pr. 15 setting should be equal to or higher than the Pr. 13 Starting frequency setting.
⋅ The JOG signal can be assigned to the input terminal using any of Pr. 178 to Pr. 189 (input terminal function selection). When terminal
assignment is changed, the other functions may be affected. Please make setting after confirming the function of each terminal.
⋅ During jog operation, the second acceleration/deceleration via the RT signal cannot be selected. (The other second
functions are valid. (Refer to page 103))
⋅ When Pr. 79 Operation mode selection = "4", push
push
to make a stop.
⋅ This function is invalid when Pr. 79 = "3" or "6".
♦ Parameters referred to ♦
⋅ Pr. 13 Starting frequency
⋅ Pr. 29 Acceleration/deceleration pattern selection
⋅ Pr. 20 Acceleration/deceleration reference frequency, Pr. 21 Acceleration/deceleration time increments
⋅ Pr. 79 Operation mode selection
⋅ Pr. 178 to Pr. 189 (input terminal function selection)
Three-phase AC
power supply
Operation
to choose the
(or
).
(or
) is pressed, the
(or
).
to choose the parameter
until Pr. 15 JOG frequency
to show the currently set
to set the value to
". (10Hz)
to set.
/
Refer to page 93
Refer to page 94
Refer to page 158
Refer to page 101
Frequency setting by external terminals
Inverter
R/L
U
1
S/L
V
Motor
2
T/L
W
3
FR-DU07
Indication
Hold down.
Release
Flicker
Parameter setting complete!!
of the PU (FR-DU07/FR-PU04/FR-PU07) to make a start or
Stop
The parameter
number read
previously
appears.
Refer to page 91
4
87

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents