Remote Setting Function (Pr. 59) - Mitsubishi Electric F700 Instruction Manual

Fr-f720-0.75k to 110k; fr-f740-0.75k to 560k
Hide thumbs Also See for F700:
Table of Contents

Advertisement

4.6.4

Remote setting function (Pr. 59)

Even if the operation panel is located away from the enclosure, you can use contact signals to perform
continuous variable-speed operation, without using analog signals.
By merely setting this parameter, you can use the acceleration, deceleration and setting clear functions of
the motorized speed setter (FR-FK).
Parameter
Name
Number
59
Remote function selection
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 156)
Inverter
Forward
rotation
STF
Acceleration
RH
Deceleration
RM
10
Clear
RL
2
SD
5
Connection
diagram for remote setting
(1) Remote setting function
⋅ Use Pr. 59 to select whether the remote setting function is used or not and whether the frequency setting storage
function in the remote setting mode is used or not.
When Pr. 59 is set to any of "1 to 3" (remote setting function valid), the functions of the RH, RM and RL signals are
changed to acceleration (RH), deceleration (RM) and clear (RL).
⋅ When the remote function is used, the output frequency of the inverter can be compensated for as follows:
External operation ... Frequency set with RH and RM operation + external operation frequency other than multi-
speed (Pr.79="3" (PU operation frequency when Pr.79="3" (external, PU combined)) and
terminal 4 input
(When making analog input compensation, set "1" to Pr. 28 Multi-speed input compensation
selection.
When Pr. 28 is set to "0" and acceleration/deceleration is made to reach the set frequency of
the analog voltage input (terminal 2 or terminal 4) by RH/RM, the auxiliary input by terminal 1
becomes invalid.)
PU operation ............. Frequency set by RH/RM operation + PU running frequency
(2) Frequency setting storage
⋅ The frequency setting storage function stores the remotely-set frequency (frequency set by RH/RM operation) into
the memory (EEPROM). When power is switched off once, then on, operation is resumed with that output
frequency value. (Pr. 59 =1)
<Frequency setting storage conditions>
⋅ Frequency at the point when the start signal (STF or STR) turns off
⋅ The remotely-set frequency is stored every one minute after one minute has elapsed since turn off (on) of both
the RH (acceleration) and RM (deceleration) signals. (The frequency is written if the present frequency setting
compared with the past frequency setting every one minute is different. The state of the RL signal does not
affect writing.)
Initial Value Setting Range
0
*
0Hz
ON
Acceleration
ON
(RH)
Deceleration
(RM)
Clear (RL)
Forward
ON
rotation (STF)
Power supply
* External operation frequency (other than multi-speed) or PU running frequency
Frequency setting by external terminals
RH, RM, RL
signal function
Multi-speed
0
setting
1
Remote setting
2
Remote setting
3
Remote setting
When Pr. 59 = 1, 2
When Pr. 59 = 3
ON
ON
ON
ON
Description
Frequency setting
storage function
Yes
No
No
(Turning STF/STR
off clears remotely-
set frequency.)
When Pr. 59 = 1
When Pr. 59 = 2, 3
Time
ON
ON
ON
ON
89
4