Mitsubishi Electric F700 Instruction Manual page 160

Fr-f720-0.75k to 110k; fr-f740-0.75k to 560k
Hide thumbs Also See for F700:
Table of Contents

Advertisement

Frequency setting by analog input (terminal 1, 2, 4)
(c) Method to adjust only the frequency without adjustment of a gain voltage (current).
(When changing the gain frequency from 60Hz to 50Hz)
Operation
1.
(Pr. 126) appears.
2.
Press
to show the currently set value.
(60.00Hz)
3.
Turn
to change the set value to
"
". (50.00Hz)
4.
Press
to set.
5.
Mode/monitor check
Press
twice to choose the
monitor/frequency monitor.
6.
Apply a voltage across the inverter
terminals 2-5 (across 4-5) and turn on the
start command (STF, STR).
Operation starts at 50Hz.
REMARKS
⋅ Changing C4 (Pr. 903) or C7 (Pr. 905) (gain adjustment) value will not change the Pr. 20 value. The input of terminal 1 (frequency
setting auxiliary input) is added to the speed setting signal.
⋅ For the operating procedure using the parameter unit (FR-PU04/FR-PU07), refer to the FR-PU04/FR-PU07 instruction
manual.
⋅ When setting the value to 120Hz or more, it is necessary to set Pr. 18 High speed maximum frequency to 120Hz or more. (Refer to
page 78)
⋅ Make the bias frequency setting using calibration parameter C2 (Pr. 902) or C5 (Pr. 904). (Refer to page 149)
Take care when setting any value other than "0" as the bias frequency at 0V (0mA). Even if a speed command is
not given, merely turning on the start signal will start the motor at the preset frequency.
♦ Parameters referred to ♦
Pr. 20 Acceleration/deceleration reference frequency
Pr. 73 Analog input selection, Pr. 267 Terminal 4 input selection
Pr. 79 Operation mode selection
152
Pr. 125) or
Flicker...Parameter setting complete!!
CAUTION
Refer to page 91
Refer to page 143
Refer to page 158
Display
or
Terminal 2 input
Terminal 4 input
Terminal 2 input Terminal 4 input

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents