4.11.4 Terminal FM, AM calibration
(Calibration parameter C0 (Pr. 900), C1 (Pr. 901))
By using the operation panel or parameter unit, you can calibrate terminal FM and terminal AM to full scale
deflection.
Parameter
Name
Number
C0(900)
FM terminal calibration
C1(901)
AM terminal calibration
*1
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 156.)
*2
The parameter number in parentheses is the one for use with the parameter unit (FR-PU04/FR-PU07).
*3
The above parameters allow its setting to be changed during operation in any operation mode even if "0" (initial value) is set in Pr. 77
Parameter write selection.
(1) FM terminal calibration (C0(Pr.900))
⋅ The terminal FM is preset to output pulses. By setting the Calibraton parameter C0 (Pr. 900), the meter connected
to the inverter can be calibrated by parameter setting without use of a calibration resistor.
⋅ Using the pulse train output of the terminal FM, a digital display ca be provided by a digital counter. The monitor
value is 1440 pulses/s output at the full-scale value of the table on the previous page (Pr. 54 FM terminal function
selection).
1mA
FM
Calibration
resistor
*1
SD
Pulse width T1: Adjust using calibration parameter C0
Pulse cycle T2: Set with Pr. 55 (frequency monitor)
*1
Not needed when the operation panel (FR-DU07) or parameter unit (FR-PU04/FR-PU07) is used for calibration.
This resistor is used when calibration must be made near the frequency meter for such a reason as a remote frequency meter.
Note that the needle of the frequency meter may not deflect to full-scale when the calibration resistor is connected. In this case, use
this resistor and operation panel or parameter unit together.
*2
The initial settings are 1mA full-scale and 1440 pulses/s terminal FM frequency at 60Hz.
⋅ Calibrate the terminal FM in the following procedure.
1) Connect an indicator (frequency meter) across the terminals FM-SD of the inverter. (Note the polarity. The
terminal FM is positive.)
2) When a calibration resistor has already been connected, adjust the resistance to "0" or remove the resistor.
3) Refer to the monitor description list (page 116) and set Pr. 54. When you selected the running frequency or
inverter output current as the monitor, preset the running frequency or current value, at which the output
signal will be 1440 pulses/s, to Pr. 55 Frequency monitoring reference or Pr. 56 Current monitoring reference. At
1440 pulses/s, the meter generally deflects to full-scale.
REMARKS
⋅ When outputting such an item as the output current, which cannot reach a 100% value easily by operation, set
(reference voltage output) and make calibration. 1440 pulses/s are output from the terminal FM.
⋅ The wiring length of the terminal FM should be 200m maximum.
CAUTION
⋅ The initial value of
the calibration parameter C0 (Pr. 900)
at 60Hz. The maximum pulse train output of terminal FM is 2400 pulses/s.
⋅ When a frequency meter is connected to across terminals FM-SD to monitor the running frequency, the FM terminal output
is filled to capacity at the initial setting if the maximum output frequency reaches or exceeds 100Hz. In this case, the
setting must be changed to the maximum frequency.
Initial Value
Indicator
1mA full-scale
analog meter
(+)
(-)
T1
8VDC
T2
Set with Pr.56 (current monitor)
Monitor display and monitor output signal
Setting Range
Calibrate the scale of the meter
connected to terminal FM.
Calibrate the scale of the analog
meter connected to terminal AM.
1440 pulses/s(+)
FM
SD
is set to 1mA full-scale and 1440 pulses/s FM output frequency
Description
(Digital indicator)
(-)
Pr. 54
to "21"
Pr. 55
123