Mitsubishi Electric F700 Instruction Manual page 266

Fr-f720-0.75k to 110k; fr-f740-0.75k to 560k
Hide thumbs Also See for F700:
Table of Contents

Advertisement

Inspection item
• Removal (FR-F740-160K or more)
1) Remove a fan cover.
2) After removing a fan connector, remove a fan block.
3) Remove a fan.
• Reinstallation (FR-F740-160K or more)
1) After confirming the orientation of the fan, reinstall the fan so that the arrow on the left of "AIR FLOW" faces
up.
2) Install fans referring to the above figure.
CAUTION
• Installing the fan in the opposite air flow direction can cause the inverter life to be shorter.
• When installing the fan, use care to prevent wires from being caught between the inverter and fan.
• Switch the power off before replacing fans. Since the inverter circuits are charged with voltage even after power
off, replace fans only when the inverter cover is on the inverter to prevent an electric shock accident.
258
2)
* The number of cooling fans differs according to the inverter capacity.
<Fan side face>
Fan *
Fan connection
connector
3)
1)
AIR FLOW