(6) Switching of command source by external terminal (X67)
⋅ In network operation mode, the command source switching signal (X67) can be used to switch the operation
command source and speed command source. This signal can be utilized to control the signal input from both the
external terminal and communication.
⋅ Set "67" to any of Pr. 178 to Pr. 189 (input terminal function selection) to assign the X67 signal to the external
terminal.
⋅ When the X67 signal is off, the operation command source and speed command source are external.
X67 Signal State
No signal assignment
ON
OFF
REMARKS
⋅ The ON/OFF state of the X67 signal is reflected only during a stop. It is reflected after a stop when the terminal is switched
during operation.
⋅ When the X67 signal is off, a reset via communication is disabled.
CAUTION
⋅ Changing the terminal assignment using Pr. 178 to Pr. 189 (input terminal function selection) may affect the other functions. Please
make setting after confirming the function of each terminal.
♦ Parameters referred to ♦
Pr. 28 Multi-speed input compensation selection
Pr. 59 Remote function selection
Pr. 79 Operation mode selection
Operation Command Source
According to Pr. 338
Operation is valid only from external terminal signal.
Refer to page 88.
Refer to page 89.
Refer to page 158.
Selection of operation mode and
Speed Command Source
According to Pr. 339
operation location
171
4