Gas Line Connection - kozy heat Alpha ALP-36-L Installation And Operation Manual

Direct vent gas fireplase
Hide thumbs Also See for Alpha ALP-36-L:
Table of Contents

Advertisement

GAS CONVERSION
This fireplace is manufactured for use with Natural Gas. An LP conversion kit, is included with fireplace.
Follow instructions included with conversion kit if converting to LP gas.
The conversion shall be carried out in accordance with the requirements of the provincial authorities having jurisdiction and in
ATTENTION
accordance with the requirements of the ANSI Z223.1 installation code.
Installation of the gas line must only be done by a qualified person in accordance with local building codes, if any.
If not, follow ANSI 223.1.
CAUTION
Commonwealth of Massachusetts: Installation must be done by a licensed plumber of gas fitter.
A listed (and Commonwealth of Massachusetts approved) 1/2" (13mm) T-handle manual shut-off valve and flexible gas
connector (included) are connected to the 1/2" (13mm) control valve inlet. If substituting for these components, please consult
local codes for compliance.
This fireplace is equipped with a 3/8"(10mm) x 18" (457mm) long flexible gas connector and manual shut-off valve. The gas
line should be run to the point of connection where the shut-off valve and flexible gas line will connect.
NOTE
The appliance and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure
testing of that system at test pressures in excess of 1/2 psi (3.5 kPa). The appliance must be isolated from the gas supply piping
system by closing its equipment shutoff valve during any pressure testing of the gas supply piping system at test pressures equal
to or less that 1/2 psi (3.5 kPa).
For high altitude installations, consult the local gas distributor or the authority having jurisdiction for proper rating methods.
The efficiency rating of this appliance is a product of thermal efficiency rating determined under continuous operating
IMPORTANT
conditions and was determined independently of any installed system.
MINIMUM INLET GAS PRESSURE
MAXIMUM INLET GAS PRESSURE
MANIFOLD PRESSURE (HI)
MANIFOLD PRESSURE (LO)
ORIFICE SIZE
INPUT BTU/hr. (kW)
MINIMUM INPUT BTU/hr. (kW)
HIGH ALTITUDE INSTALLATIONS
In the USA: The appliance may be installed at higher altitudes. Please refer to your American Gas Association
guidelines which state: the sea level rated input of Gas Designed Appliances installed at elevations above 2000ft. (610m)
is to be reduced 4% for each 1000ft. (305m) above sea level. Refer also to National Fuel Gas Code, ANSI Z223.1/ NFPA
ATTENTION
54, local authorities, or codes which have jurisdiction in your area regarding the de -rate guidelines.
In Canada: When the appliance is installed at elevations above 4500ft. (1372m), the certified high altitude rating shall
be reduced at the rate of 4% for each additional 1000ft. (305m). Refer also to CSA-B149.1 Natural Gas and Propane
Installation Code, Local authorities, or codes which have jurisdiction in your area regarding the de-rate guidelines.

GAS LINE CONNECTION

NATURAL GAS
5" WC (1.25 kPa) (7" WC (1.74 kPa) recommended)
10.5" WC (2.62 kPa)
3.5" WC (.87 kPa)
1.6" WC (.40 kPa)
#29
48,000 BTU/hr (14.07 kW)
32,500 BTU/hr (9.53 kW)
LP GAS
11" WC (2.74 kPa) (recommended)
13" WC (3.24 kPa)
10" WC (2.49 kPa)
6.4" WC (1.59 kPa)
#47
46,500 BTU/hr (13.63 kW)
37,000 BTU/hr (10.84 kW)
17