Field Settings
2.7

Setting the Filter Counter

1
Mode No. 10 or 20
First code No. 0
3
4
Fan speed setting at
thermostat OFF
5
4–16
When the filter counter indication time is set to ON, set the second code No., according to the table
below
Unit
Mode No.
FCQ
FFQ
FHQ
FUQ
10 or 20
FAQ
FBQ
FDQ, FDEQ
When the cool/heat thermostat is OFF, you can stop the indoor unit fan by switching the setting to
"Fan OFF". This setting is used as a countermeasure against odour, for example for barber shops and
restaurants.
You can switch the fan speed to the set fan speed when the heating thermostat is OFF. This setting is
called "Set Fan Speed" . Default the fan speed is set LL to prevent cold draft.
Note: That a combination of modes 11 (21) and 12 (22) is required to enable following settings:
Mode No. - First code No.
12 (22) - 3
12 (21) - 2
01
Second
02
code No.
First code No.
Second code No.
0
Second code No.
01
02
Cool: Set Speed
Cool: Set Speed
Head: LL Speed
Head: Set Speed
Cool: OFF + moni-
Cool: OFF + moni-
toring at set speed
toring at set speed
Heat: OFF + moni-
Heat: Set speed
toring at LL speed
ESIE05-04
Contamination
01
02
light
heavy
±2500 hrs
±1250 hrs
±2500 hrs
±1250 hrs
±2500 hrs
±1250 hrs
±2500 hrs
±1250 hrs
±200 hrs
±100 hrs
±2500 hrs
±1250 hrs
±2500 hrs
±1250 hrs
03
Cool: Set Speed
Head: Continu-
ously OFF
Cool: OFF +moni-
toring at set speed
Heat: OFF + moni-
toring at OFF
Part 4 – Commissioning and Test Run