Error Codes
2.5
Indoor Unit Fan Motor Lock (A6)
1
Error code
LED indications
3
3
Error generation
Causes
4
5
3–36
A6
The table below shows the LED indications.
Operation
Normal
Malfunctioning
The error is generated when the fan rotations are not detected while the output voltage to the fan is at
its maximum.
The possible causes are:
Malfunctioning indoor unit fan motor
Broken or disconnected wire
Malfunctioning contact
Malfunctioning indoor unit PCB.
HAP (green)
c
c
ESIE05-04
HBP (green)
c
c
Part 3 – Troubleshooting