General Operation Data - Daikin FCQ35B7V1 Service Manual

Hide thumbs Also See for FCQ35B7V1:
Table of Contents

Advertisement

Test Run and Operation Data
3.1

General Operation Data

1
Guide Lines for
Optimal Operation
Condition
Indoor Unit Fan:
3
4
5
4–24
The operation value guide lines when operating under standard conditions (at Rated frequency) by
pushing the test run button on the remote controller are as given in the table below.
"H" Operation Compressor: Rated Frequency
High
Low
Pressure
Pressure
(Mpa)
(Mpa)
Cooling
26 bar ~
6 bar ~
34 bar
10 bar
Heating
25 bar ~
5.3 bar ~
32.6 bar
9.5 bar
Discharge
Suction
Pipe
Temperature
Temperature
(°C)
(°C)
60~100
–2~10
60~100
–6~2
Part 4 – Commissioning and Test Run
ESIE05-04
Indoor Unit
Outdoor Unit
Side:
Side:
Differential
Differential
Between
Between
Suction Tem-
Suction Tem-
perature and
perature and
Discharge
Discharge
Temperature
Temperature
(°C)
(°C)
8~18
7~12
14~30
2~6