Functional concept
1.5

Simulated Operation Function

1
Outline
2
Sensors
3
Remark
4
5
2–8
When a malfunction on one of the below thermistors occurs, operation will continue while displaying
the applicable alarm on the remote-controller. Fin thermistor malfunction is only displayed when
pressing the "Inspection" button on the remote-controller.
Outside temperature thermistor
Outdoor heat exchanger thermistor
Fin thermistor
Discharge pipe thermistor
Indoor unit air suction thermistor
Indoor heat exchanger thermistor
Simulated operation will not be conducted in case the low pressure sensor or suction thermistor is
malfunctioning.
ESIE05-04
Part 2 – Functional Description