Daikin FCQ35B7V1 Service Manual page 219

Hide thumbs Also See for FCQ35B7V1:
Table of Contents

Advertisement

ESIE05-04
4.5
Resistance Conversion Table (Ambient, Coil, Fin)
Temperature –
The table below is the thermistor (R1T and R2T) temperature – resistance conversion table.
resistance
Temp.
(°C)
Applicable sensors
A: Indoor: R1T, R2T, R3T
Part 3 – Troubleshooting
Temp.
A (kΩ)
(°C)
-20
197.81
20
-19
186.53
21
-18
175.97
22
-17
166.07
23
-16
156.80
24
-15
148.10
25
-14
139.94
26
-13
132.28
27
-12
125.09
28
-11
118.34
29
-10
111.99
30
-9
106.03
31
-8
100.41
32
-7
95.14
33
-6
90.17
34
-5
85.49
35
-4
81.08
36
-3
76.93
37
-2
73.01
38
-1
69.32
39
0
65.84
40
1
62.54
41
2
59.43
42
3
56.49
43
4
53.71
44
5
51.09
45
6
48.61
46
7
46.26
47
8
44.05
48
9
41.95
49
10
39.96
50
11
38.08
51
12
36.30
52
13
34.62
53
14
33.02
54
15
31.50
55
16
30.06
56
17
28.70
57
18
27.41
58
19
26.18
59
Additional Checks for Troubleshooting
A (kΩ)
Temp.
A (kΩ)
(°C)
25.01
60
4.96
23.91
61
4.79
22.85
62
4.62
21.85
63
4.46
20.90
64
4.30
20.00
65
4.16
19.14
66
4.01
18.32
67
3.88
17.54
68
3.75
16.80
69
3.62
16.10
70
3.50
15.43
71
3.38
14.79
72
3.27
14.18
73
3.16
13.59
74
3.06
13.04
75
2.96
12.51
76
2.86
12.01
77
2.77
11.52
78
2.68
11.06
79
2.60
10.63
80
2.51
10.21
9.81
9.42
9.06
8.71
8.37
8.05
7.75
7.46
7.18
6.91
6.65
6.41
6.65
6.41
6.18
5.95
5.74
5.14
1
3 3
4
5
3–57

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents