Overview Of The Indoor Safety Devices - Daikin FCQ35B7V1 Service Manual

Hide thumbs Also See for FCQ35B7V1:
Table of Contents

Advertisement

Troubleshooting
1.10

Overview of the Indoor Safety Devices

1
FCQ35, 50, 60, 71B
FCQ100, 125B
FCQ71, 100, 125, 140D
FFQ25, 35, 50, 60B
3
3
FBQ35, 50, 60, 71,100, 125B
FDQ125, 200, 250B
FHQ35, 50, 60, 71, 100, 125B
FUQ71, 100, 125B
4
FAQ71, 100B
FDEQ71, 100, 125B
5
3–30
Thermal protector
Abnormal
>130°C +/-5°C
>140°C +/-5°C
N.A.
>130°C +/-5°C
N.A.
N.A.
>130°C +/-5°C
>130°C +/-5°C
>130°C +/-5°C
N.A.
Reset (automatic)
<83°C +/-20°C
<45°C +/-15°C
N.A.
<83°C +/-20°C
N.A.
N.A.
<83°C +/-20°C
<83°C +/-20°C
<83°C +/-20°C
N.A.
ESIE05-04
Thermal fuse fan motor
N.A.
N.A.
N.A.
N.A.
>152 +/-2°C
>160 °C
N.A.
N.A.
N.A.
>152 +/-2°C