ESIE05-04
1.9
Forced Thermostat OFF
Outline
The unit will perform the forced thermostat off function in following conditions:
Condition 1
Thermostat off due to freeze-up prevention.
(cooling)
Prevent the indoor unit heat exchanger from freezing in cooling operation when one of the below
conditions is applicable:
Condition 2
Thermostat off due to high outdoor temperature.
(heating)
When the outside temperature is > 30°CDB in heating mode, the unit will conduct a forced thermostat
off operation to protect the system.
Reference
"Freeze Prevention Function". Refer to page 2-14.
Part 2 – Functional Description
Indoor unit heat exchanger temperature < -5°C for 1 minute continuously.
Indoor unit heat exchanger temperature < -1°C for 40 minutes accumulated.
Functional concept
1
2
3
4
5
2–13