Field Settings
2.3
How to Change the Field Settings with the Wireless Remote Controller
1
Optional
accessories
Wireless remote
controller
3
4
5
Setting
4–12
If optional accessories are mounted on the indoor unit, the indoor unit setting may have to be changed.
Refer to OH98-2 or the installation manual (optional handbook) for each optional accessory.
The illustration below shows the wireless remote controller.
Mode No.
Field setting mode
RESERVE button
First code No.
Second code No.
To set the field settings, you have to change:
"Mode No."
"First code No."
"Second code No.".
To change the field settings, proceed as follows:
Step
Action
1
Hold down the INSPECTION/TEST button for at least 4 s during normal mode to enter
the "Field setting mode".
2
Press the MODE button to select the desired "Mode No.".
3
Press the UP button to select the "First code No.".
4
Press the DOWN button to select the "Second code No."
5
Press the RESERVE button to set the present settings.
6
Press the INSPECTION/TEST button to return to the "Normal mode".
ESIE05-04
UP button
DOWN button
MODE button
INSPECTION/TEST button
Part 4 – Commissioning and Test Run