Air Flow Direction Setting; Filter Sign Setting - Daikin Skyair FHC35K Service Manual

Cooling only heat pump split-system air conditioner skyair r(y)k&f series addition of fuy, fvy-l, fay-fa, fhyc140kve models r71, 100kval, r125ktal models
Table of Contents

Advertisement

Si-71A
„ In the Case of FHYC (100 to 140 class)
Ceiling
Height
1.5.3

Air Flow Direction Setting

Set the air flow direction of indoor units as given in the table below. (Set when optional air outlet blocking
pad has been installed.) The second code No. is factory set to "01."
Setting Table
1.5.4

Filter Sign Setting

If switching the filter sign ON time, set as given in the table below.
Set Time
Setting
Contamination Light
Contamination Heavy
*FH(Y)C and FH(Y) only are 1,250 hrs.
1.5.5
Wireless Setting (Address and MAIN/SUB Setting)
Explanation
If several wireless remote controller units are used together in the same room (including the case where
both group control and individual remote controller control are used together), be sure to set the addresses
for the receiver and wireless remote controller. (For group control, see the attached installation manual for
the indoor unit.) If using together with a wired remote controller, you have to change the main/sub setting or
the receiver.
Setting The
Through the small opening on the back of the receiver, set the wireless address switch (SS2) on the printed
Receiver
circuit board according to the table below.
Wireless Address Switch
(SS2)
When using both a wired and a wireless remote controller for 1 indoor unit, the wired controller should be
set to MAIN. Therefore, set the MAIN/SUB switch (SS1) of the receiver to SUB.
MAIN/SUB Switch (SS1)
Explanation of Field Set
Standard (N)
Lower than 3.2 m
High Ceiling c
Lower than 3.6 m
(H)
Higher Ceiling d
Lower than 4.2 m
(S)
Mode No.
First Code No.
13 (23)
1
Filter Specs.
Unit No.
Method of Field Set (Reset after Maintenance Inspection/Repair)
No. of Air Outlets Used
4-way Outlets
3-way Outlets
Lower than 3.6 m
Lower than 4.0 m
Lower than 4.2 m
Second Code No.
01
F : 4-direction air flow
02
T : 3-direction air flow
03
W : 2-direction air flow
Long Life
2,500 hrs.
1,100 hrs. *
No.1
MAIN
2-way Outlets
Lower than 4.2 m
Lower than 4.2 m
Setting
Standard
Urtra Long Life Filter
200 hrs.
10,000 hrs.
100 hrs.
5,000 hrs.
No.2
SUB
No.3
25