Fcq71, 100, 125B - Daikin FCQ35B7V1 Service Manual

Hide thumbs Also See for FCQ35B7V1:
Table of Contents

Advertisement

ESIE05-04
6.3

FCQ71, 100, 125B

PCB
The illustration below shows the PCB connectors.
X20A
Connectors
The table below describes the PCB connectors.
Connector
X5A
X10A
X11A
X15A
X18A
X19A
X20A
X24A
X25A
X27A
X33A
X35A
X36A
X40A
X60A
X61A
Part 1 – System Outline
X27A
X11A
X11A
X10A
X25A
Connected to
Description
X1M
Terminal strip for P1/P2
T1R
Transformer secondary side
T1R
Transformer primary side
S1L
Float switch
R2T
Coil thermistor (liquid)
R1T
Air thermistor
M2F
Fan motor (power supply)
X2A on A3P
X24A is connected when the wireless remote control is used.
M3P
Drain pump motor
X2M
Power supply & communication
X1A on KRP1B
Connector for wiring adaptor KRP1B
X1A on KRP4
Connector to group control adaptor power supply (16VDC) for
optional PCB KRP4
M1A
Swing flap motor
Connector for remote ON/OFF, Forced OFF
X1A on DTA112
Connector for interface adaptor
X2A on DTA112
Connector for interface adaptor
X33A
X19A
X60A X61A
X18A
X36A
X40A
PCB Layout
1
X5A
X35A
X24A
3
X15A
4
5
1–109