ESIE05-04
1.14

Condensation Avoidance Control

Purpose
Avoid condensation on the swing flap when the most downward position of the swing flap (position 4)
is selected on the remote controller.
Applicable units
This function is applicable for the FHQ units only.
Method
The condensation avoidance control will function in the following operating modes:
Method
To avoid condensation on the swing flap, the condensation avoidance control is activated:
Stage
1
2
3
4
Part 2 – Functional Description
Cooling (automatic)
Dry keep.
Description
The fan operates in cooling mode with the blade in downward position (set on the remote
control).
After 30 min, the blade moves to a horizontal position.
After 1 h operation in horizontal position, the blade moves back to its downward position
for 30 min.
The unit operation is reset by:
Changing the operating mode into "heating" or "fan"
Changing the air flow direction
Turning the unit operation OFF and ON.
Functional concept
1
2
3
4
5
2–19