Functional concept
1.2
Functions of Thermistors
1
Locating the
thermistors
2
3
4
5
Remark
Functions of the
thermistors
2–4
Sensor R3T on indoor coil of FCQ35~60B7V1, FFQ35~60BV1, FBQ35~60B7V1 & FHQ35~60BUV1
is not used when the indoor units are connected to sky-air outdoor units (RR, RQ, RZQ).
Ther-
Wiring
Location
mistor
symbol
1
Indoor air
R1T
return
2
Indoor
R2T
heat
exchanger
3
Indoor
R3T
heat
exchanger
R3T
R2T
Mode
Function
Cooling
Thermostat control
PMV control
General frequency control
Heating
Thermostat control
PMV control
General frequency control
Cooling
Compressor frequency control (target Te)
Inverter current protection control
Freeze-up control
Heating
Compressor frequency control (target Tc)
Inverter current protection control
Hot start control
Peak cut-off
Heating
Peak cut-off
ESIE05-04
R1T
Part 2 – Functional Description