Appendix Function Parameter List
■ Reset Lock Function
When a fault trip occurs, clearing of fault trip status with stop signal is disabled
to perform reset operation with SW signal after identifying the details of fault
trip and eliminating the abnormality.
・Normally, SW signal is input with ON status.
・When a fault trip occurs, the inverter will maintain the trip status even if stop
signal and reset signal are input.
・After the abnormality is identified and eliminated, the fault trip will be reset
when this SW is turned OFF.
* Turn reset lock signal OFF and press STOP button to reset the fault.
In addition, turn the fault reset signal OFF.
175