Appendix Function Parameter List
・The factory setting is "1" (OP stop).
・If the value is set to "0", operation will start immediately after the power is
turned ON.
・If the value is set to "2", operation will start when the power is turned ON and
after the waiting time has elapsed.
Setting
Operation
value
0
Run
1
"OP" stop
Run after
2
waiting time
elapses
3
"OP stop"
・Waiting time can be set with parameter P026.
Related parameter: P026
164
Operation starts immediately when the low voltage level (LU
level) is exceeded after the power is turned ON.
OP trip occurs when the low voltage level (LU level) is
exceeded after the power is turned ON.
Turn the run signal OFF once, perform reset operation and
turn the run signal ON again to start operation.
Operation starts when the low voltage level (LU level) is
exceeded and the waiting time has elapsed after the power is
turned ON.(The waiting time can be set with parameter P026.)
OP trip occurs when the low voltage level (LU level) is
exceeded after the power is turned ON.
Turn the run signal OFF once, perform reset operation and
turn the run signal ON again to start operation.
(The setting will function in the same manner as data "1" with
run signal ON when the power is turned ON. However,
starting after the waiting time has elapsed is possible during
normal startup.)
Details of operation