Panasonic VF200 Instruction Manual page 197

Table of Contents

Advertisement

Appendix Function Parameter List
P042
JOG Frequency
JOG Acceleration Time
P043
JOG Deceleration Time
P044
Operating frequency and acceleration/deceleration time during JOG operation
can be set.
■ Parameter P042: JOG Frequency
Data setting range
(Hz)
■ Parameter P043: JOG Acceleration Time
Data setting range (s)
Increment (s)
The display code for 0.04 s is "0000".
·
■ Parameter P044: JOG Deceleration Time
Data setting range (s)
Increment (s)
The display code for 0.04 s is "0000".
·
"Run command select" must be set to external control. (Parameter P003 can
·
be set to "2~5".)
"SW function select" must be set to "JOG function".
·
When SW set to JOG function is turned ON, the inverter will enter JOG
·
operation ready status.
Perform JOG run/stop and forward/reverse run with terminal No.2 and No.3.
·
Refer to function descriptions on page 172.
·
JOG frequency under vector control is 1 Hz to 120 Hz.
·
Related parameters: P003, P036 to P040
190
0.5 to 400.0
0.04· 0.1 to 3600
0.1 (0.1 to 999.9), 1 (1000 to 3600)
0.04· 0.1 to 3600
0.1 (0.1 to 999.9), 1 (1000 to 3600)