P008
Max. Output Frequency
Base Frequency
P009
Maximum output frequency and base frequency can be set.
(Parameter P005 is valid only when "FF" or "3C" is set.)
■ Parameter P008: Max. Output Frequency
Data setting range
(Hz)
■ Parameter P009: Base Frequency
Data setting range
(Hz)
・If "P005: V/F Mode" is set to "50" or "60", the maximum output frequency and
base frequency will become fixed values.
・Frequency higher than "P100: Upper Frequency Limit" cannot be output.
・If a general-purpose motor with rated frequency of 50/60 Hz is running at a
frequency exceeding the ratings, the motor may be damaged. Therefore,
please set a frequency that matches with motor characteristics.
・If base frequency is required to be changed simutaneously with maximum
output frequency for a dedicated high-speed motor etc., such change should
be made with the parameter.
・When running a general-purpose motor at a frequency higher than universal
frequency, the base frequency setting should not exceed the rated output
frequency (50/60 Hz) of the motor.
・When a general-purpose motor reaches a level higher than the base
frequency (normally 50/60 Hz), the motor will show constant output
characteristics and the generated torque will drop in reverse proportion to the
frequency.
Related parameters: P005, P100
50.0 to 400.0