Appendix Function Parameter List
P090
Output TR1 Function Select
Output TR2 Function Select
P091
Functions of open-collector output 1 (control circuit terminal No.10 to No.12)
and open-collector output 2 (control circuit terminal No.11 to No.12) can be
set.
TR1P090 TR2P091
0
1
2
3
4
5
Setting
value
6
7
8
9
10
11
212
Function
0
Run signal
Reverse run
1
signal
2
Arrival signal
3
Overload alarm
Frequency
4
sensing
Current sensing
5
(1)
Current sensing
6
(2)
7
Fault alarm (1)
8
Fault alarm (2)
After one cycle of
9
timer operation
Timer operation
10
completed
11
Alarm
ON conditions for open-collector
output
With run signal ON or during inverter
output
When inverter is in reverse run status
When output frequency is within ±2
Hz of setting frequency
When the output current is above
140% of the rated current or the
electronic thermal level is reached.
When the output frequency is above
sensing frequency (parameter P093
setting).
When the output current is above the
sensing current level (parameter
P095 setting).
When the output current is below the
sensing current level (parameter
P095 setting).
When fault trip occurs in the inverter
When the inverter is in normal status
(OFF for fault trip status)
When one cycle of timer operation
completes (output is available only
during waiting time)
When timer operation completes
(with "tEnd" displayed)
Output is available with alarm LED
flickering.