Appendix D: Power Supply & Batteries
Use the form below to determine the required main chassis and secondary power supply (batteries).
The main AC branch circuit connection for Fire Alarm Control Unit must provide a dedicated continuous power
without provision of any disconnect devices. Use #12 AWG wire with 600-volt insulation and proper over-current
circuit protection that complies with the local codes. Refer to Appendix A on page 75 for specifications.
Model Number
Description
QIF-5000B
Interface
QAA-5160-70/25
1 Zone 60W Amplifier
QAA-5230-70/25
2 Zone 30W Amplifier
QAA-5230S-70/25
2 Zone 30W Amplifier (split)
QAA-5230S-525-
2 Zone 30W Amplifier (split)
70/25
QAA-5415-70
4 Zone 15W Amplifier, 70V
QAA-5415-25
4 Zone 15W Amplifier, 25V
Master Paging Module
QMP-5100B/QMP-5101B
QMP-5100AX
Paging Multiplex Module
QMP-5100MSB
Microphone Splitter Board
QZP-5101
Paging Zone Module
Master Telephone Module
QMT-5300A/QMT-5302
QZT-5302
Telephone Zone Module
QIF-1000
Interface Module
QIF-2000
Interface Module
QDV-1000
Digitized Voice Module
Total audio power in watts
Total audio power in watts for QAA-5415-70 or -25
Total currents (Add above currents)
Total Current Requirement: ALARM (B)______ Amps.
Battery Capacity Requirement
([STANDBY (A) ______ ] X [(24 or 60 Hours) ___ ]) + ([ALARM (B) ______ ] X [
Battery Selection: Multiply answer above (C) by 1.20 to derate battery.
Batteries: BA-124 (24AH), BA-140 (40AH), and BA-165(65AH).
Above 40AH, batteries require a separate box (model BC-160).
Use 0.084 for five minutes of alarm or 0.5 for thirty minutes of alarm as a multiplier figure.
IMPORTANT NOTICE
Power Requirements (All currents are in amperes)
Standby
Qty
(Amps)
1
X
0.200
X
0.055
X
0.055
X
0.055
X
0.055
X
0.055
X
0.055
X
0.031
X
0.031
X
0.130
X
0.010
X
0.040
X
0.026
X
0.180
X
0.010
X
0.030
STANDBY
Alarm in Hr.] _____) = (C) ______AH
QX-5000 Series Installation and Operation Manual
Total
Alarm
Standby
(Amps)
(Amps)
=
0.200
=
0.350
=
0.350
=
0.350
=
0.350
=
0.350
=
0.350
=
0.081
=
0.081
=
0.275
=
0.015
=
0.040
=
0.026
=
0.200
=
0.010
=
0.030
0.065/watt
0.075/watt
(A)
Total
Alarm
(Amps)
=0.200
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
(B)
85