QMP-5100B and QMP-5101B Paging Configuration

As shown in previous figures, the QMP-5100B and QMP-5101B configuration DIP switches SW1 & SW2 are
located on the bottom right corner of the module.
Note: "OFF" means the switch is in the OFF or open position, "ON" means it is in the ON
or closed position.
DIP Switch
DIP SWITCHES SW1-1 TO SW1-4 ARE USED FOR MULTIPLE QMP-5100Bs, ADDRESSES 1 TO 15
and Position
1
1
ON
2
OFF
3
OFF
4
.OFF
5
For automatic All Call (when PTT is pressed), set to ON, otherwise leave OFF.
DIP
switch
Microphone Pre-Announce Tone:
SW-1
6
OFF = no tone, ON = tone present
Master Telephone:
7
OFF = not present, ON = present
Paging Selector Panel:
8
Always OFF
1
Not used, must be left OFF.
2
Not used, must be left OFF.
3
Not used, must be left OFF.
DIP
4
Not used, must be left OFF.
switch
5
Not used, must be left OFF.
SW-2
6
Not used, must be left OFF.
7
Not used, must be left OFF.
8
Not used, must be left OFF.
2
3
4
5
OFF
ON
OFF
ON
ON
ON
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
QX-5000 Series Installation and Operation Manual
Function
6
7
8
9
OFF
ON
OFF
ON
ON
ON
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
ON
ON
10
11
12
13
OFF
ON
OFF
ON
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
14
15
OFF
ON
ON
ON
ON
ON
ON
ON
45

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the QX-5000 Series and is the answer not in the manual?

Questions and answers

Table of Contents