Administering the SNMP modules

To administer the SNMP modules:
1. Make sure the UPS is plugged into a nonswitched electrical outlet.
2. Connect the services laptop computer (RS-232 serial port) to the DB-9 connector on the
back of the SNMP module for UPS 1 using the DB-9 to DB-9 serial cable supplied with the
SNMP module.
Note:
Avaya Terminal Emulation and HyperTerminal are supported terminal emulation
Note:
applications.
3. On the services laptop open a VT-100 terminal emulation session.
4. Administer the terminal emulation port settings:
9600 baud
No parity
8 data bits
1 stop bit
No flow control
5. Follow the instructions in the User's Guide.
6. Set the following parameters:
IP address and subnet mask of the UPS. (defaults are 198.152.254.239, 255.255.255.0.)
IP address of the trap receiver. (default is 198.152.254.200)
Default Gateway address of the UPS is 198.152.254.201.
Note:
If a Network Management System (NMS) is going to monitor the UPS, coordinate
Note:
the assignment of community names with the network administrator. If an NMS is
not going to monitor the UPS, set the community names to unique string values.
SNMP community string for Get, Set, and Trap.
Configuring the SNMP modules in the UPS
Issue 3.1 June 2005
33