Fuse Replacement; Specifications - Toro TIS-240 User Manual

Intelli-sense 24-station irrigation system controller
Table of Contents

Advertisement

Fuse Replacement

!
WARNING: The fuse protects the transformer from overload due
to a short circuit condition. For continued protection against risk of
fire or controller damage, replace only with a fuse of the same type
and rating.
Ensure ower is OFF prior to removing/replacing the fuse.
1. Disconnect power to the controller.
2. Unlatch and swing open the control module.
3. Carefully remove the blown fuse from the PC board.
4. Clip in a new 2A Slow-Blow
5. Close and latch the control module.
6. Restore power to the controller.
Specifications
Mechanical
• Cabinet: 8.50" H x 11.5" W x 5.625" D
• Wiring conduit provisions: Power - 0.50" Field - 2.00" Aux. - 0.50"
• Operating Temperature Range – 32°F to 140°F (0°C to 60°C)
• Storage Temperature Range – -22°F to 149°F (-30°C to 65°C)
Electrical
• Input: 120 VAC., 50/60 Hz, 0.5A
• Output: 24 VAC, 50/60 Hz, 50 VA (1.25A) max. total, 0.5A max. per station
• Master Valve/Pump Start Relay Output: 24 VAC, 0.325A max.
• Sensor Input: Normally-closed Rain Sensor (bypass switch provided)
• Fuse: 250V, 2.0A, Slow-Blow (102-3406)
76
p
fuse
(P/N 102-3406).