RZQ200 · 250C7Y1B
1.8
Procedure for Removal of Thermistor
Procedure
Step
Remove the front panel
(middle, bottom) according
to the procedure for
"Removal Related to
Outside Panel".
1. Remove the outdoor air
temperature thermistor
Apply the principle of
1
leverage to remove the
clamps.
Pull out the fixture from
2
the outdoor air
temperature thermistor.
2. Remove the suction pipe
thermistor
Cut the clamps
1
(2 places) for the heat
shield.
Push the lower part of
2
the mounting spring to
pull out the suction pipe
thermistor.
3. Remove the discharge
pipe thermistor
1
Cut the clamps
(one place) for the heat
shield.
Push the lower part of
2
the mounting spring to
pull out the discharge
pipe thermistor.
202
Warning
Be sure to commence the disassembling work after 10 minutes or
more elapsed from all power supplies have been turned off.
Procedure
Suction pipe
Discharge pipe
thermistor (R2T)
thermistor (R3T)
Outdoor air temperature
thermistor (R1T)
Outdoor air
temperature thermistor
Thermistor bottom Mounting spring
SiBE26-701
Points
Removal of the outdoor air
temperature thermistor
Hook
Hook
Outdoor air
temperature thermistor
Removal of the suction pipe
thermistor
Heat shield
Removal of the discharge
pipe thermistor
Mounting spring
Heat
shield
Thermistor
Removal Procedure