Procedure for Removal of Fan Motor

Procedure
Step
Remove the top panel
assy and front panel
(middle) according to the
procedure for "Removal
Related to Outside Panel".
1. Remove the propeller fan
Loosen the four
1
mounting screws (M10)
using a hexagonal
wrench (5mm).
2
Pull up the propeller
fan.
2. Remove the fan motor
1
Unscrew the four
screws, and then slide
below the electrical
component box (cover)
to remove it.
2
Remove the relay
connector (X1A, X2A)
for the fan motor (M1F).
Remove the tie-wraps
3
that fix the lead wire.
Unscrew the four bolts
4
that fix the fan motor to
remove the fan motor.
Removal Procedure
Warning
Be sure to commence the disassembling work after 10 minutes or
more elapsed from all power supplies have been turned off.
Procedure
Propeller fan
Electrical
component box
(cover)
Fan motor
Lead wire
Clamp
Hexagonal
wrench
Mounting
screw
Precaution for mounting the
fan:
The hub has a D-shaped
hole.
Use the D-shaped cover as
a guide when mounting the
fan.
Relay connector joint
Relay
connector
(power wire)
Relay
connector
(signal wire)
RZQ200 · 250C7Y1B
Points
Cover
D-shaped shaft
195