A6" Malfunction Of Indoor Unit Fan Motor - Daikin SkyAir RZQ200 · 250C7Y1B Service Manual

R-410a heat pump 50hz
Table of Contents

Advertisement

SiBE26-701
4.6

"A6" Malfunction of Indoor Unit Fan Motor

A6
Remote
Controller
Display
Applicable
FAQ100, FHQ
Models
Method of
To be detected based on transmission failure of the signal by the fan motor for detecting the
Malfunction
number of rotation
Detection
Malfunction
When number of rotation can not be detected even at the maximum output voltage to the fan
Decision
Conditions
Supposed
Causes
Troubleshooting
Troubleshooting
Defective indoor unit fan motor
Disconnection
Defective contact
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Are X20A and
NO
X 26A securely
connected?
YES
Unplug
X26A with
power being
supplied, to check if
YES
direct current voltage of
approx.12V is supplied
between the pins
1 and 3 of
X26A.
NO
Diagnosis by Remote Controller
Correctly connect these.
Check if defective
connection for the
connectors or
disconnection are
found.
Check the fan motor
of the indoor units
and the wiring circuit
of the motor.
Replace the indoor unit
PC board.