Daikin SkyAir RZQ200 · 250C7Y1B Service Manual page 190

R-410a heat pump 50hz
Table of Contents

Advertisement

SiBE26-701
1. Power module checking
When using the analog type of multiple
tester, make measurement in resistance
measurement mode in the x1k
2. Diode module checking
When using the analog type of multiple
tester, make measurement in resistance
measurement mode in the x1k
Troubleshooting
Measuring
point
No.
Criterion
+
-
1
P3
U
2
P3
V
2 to 15kΩ
3
P3
W
4
U
P3
5
V
P3
Not less
6
W
P3
than
15kΩ
7
N3
U
(including)
8
N3
V
9
N3
W
10
U
N3
11
V
N3
2 to 15kΩ
12
W
N3
Measuring
point
No.
Criterion
+
-
1
P1
J1
2
P1
J2
2 to 15kΩ
3
P1
J3
4
J1
P1
5
J2
P1
Not less
6
J3
P1
than
15kΩ
7
N3
J1
(including)
8
N3
J2
9
N3
J3
10
J1
N3
11
J2
N3
2 to 15kΩ
12
J3
N3
When using the digital type of multiple
tester, make measurement in diode check
Ω
range.
mode (
Remark
No.
1
2
3
4
It may take
5
time to
6
determine the
resistance due
7
to capacitor
8
charge or else.
9
10
11
12
When using the digital type of multiple
tester, make measurement in diode check
Ω
range.
mode (
Remark
No.
1
2
3
4
It may take
5
time to
6
determine the
resistance due
7
to capacitor
8
charge or else.
9
10
11
12
Diagnosis by Remote Controller
).
Measuring
point
Criterion
+
-
P3
U
Not less
It may take time to
than
determine the voltage
P3
V
1.2V
due to capacitor
P3
W
(including)
charge or else.
U
P3
V
P3
W
P3
0.3 to 0.7V
N3
U
N3
V
N3
W
U
N3
Not less
It may take time to
than
determine the voltage
V
N3
1.2V
due to capacitor
W
N3
(including)
charge or else.
).
Measuring
point
Criterion
+
-
P1
J1
Not less
It may take time to
than
determine the voltage
P1
J2
1.2V
due to capacitor
P1
J3
(including)
charge or else.
J1
P1
J2
P1
J3
P1
0.3 to 0.7V
N3
J1
N3
J2
N3
J3
J1
N3
Not less
It may take time to
than
determine the voltage
J2
N3
1.2V
due to capacitor
J3
N3
(including)
charge or else.
Remark
Remark
179