List Of Electrical And Functional Parts; Outdoor Unit - Daikin SkyAir RZQ200 · 250C7Y1B Service Manual

R-410a heat pump 50hz
Table of Contents

Advertisement

SiBE26-701

3. List of Electrical and Functional Parts

3.1

Outdoor Unit

RZQ200 · 250C7Y1B
Item
Name
Type
Inverter
OC protection
device
Output
Fan
Fan motor
OC protection
device
For main
For noise filrer
For inverter power supply
For fan driver
For QA transfer
Electronic expansion valve(Main)
Electronic expansion valve(Subcool)
High pressure
For M1C
switch
Low pressure sensor
Fusible plug
Discharge gas temperature
protection(Disharge gas thermistor)
Inverter fin temperature
protection(Radiator fin thermistor)
For main PC
board
For noise filter PC
Fuse
board
For QA transfer
PC board
Function and Operation
Symbol
RZQ200C7Y1B
M1C
M1F
A1P
A2P
A3P
A4P
A6P
Y1E
Fully closed: 0 pulse, Fully open: 480 pulse
Y2E
Fully closed: 0 pulse, Fully open: 480 pulse
S1PH
S1NPL
R3T
R1T
F1U
F2U
F400U
F3U

List of Electrical and Functional Parts

Model
RZQ250C7Y1B
JT1GCVDKR@T
14.7A
0.75kW
3A
EC0676
FN354-H-1
PC0509-1
PC0511-1
EC0663
OFF: 4.0MPa ON: 3.0MPa
OFF: 0.07MPa
70~75°C
OFF: 135°C
OFF: 87°C
T 3.15A 250V
T 3.15A 250V
T 6.3A 250V
T 6.3A 250V