Field Setting Of Indoor Unit; Field Setting From Remote Controller - Daikin SkyAir RZQ200 · 250C7Y1B Service Manual

R-410a heat pump 50hz
Table of Contents

Advertisement

Field Setting of Indoor Unit

1. Field Setting of Indoor Unit

1.1

Field Setting from Remote Controller

Individual function of indoor unit can be changed from the remote controller. At the time of
installation or after service inspection / repair, make the local setting in accordance with the
following description.
Wrong setting may cause malfunction.
(When optional accessory is mounted on the indoor unit, setting for the indoor unit may be
required to change. Refer to information in the option handbook.)
1.1.1 Wired Remote Controller
BRC1D52 type
1. When in the normal mode, press the "
2. Select the desired MODE NO. with the "
3. During group control, when setting by each indoor unit (mode No. 20, 21, 22 and 23 have
4. Push the "
5. Push the "
6. Push the "
7. Push the "
(Example)
If during group setting and the time to clean air filter is set to FILTER CONTAMINATION,
HEAVY, SET MODE NO. to "10" FIRST CODE NO. to "0", and SECOND CODE NO. to "02".
24
5
4
1, 2, 7
FIELD SET MODE is entered.
been selected), push the "
operation is unnecessary when setting by group.)
" upper button (4) and select FIRST CODE NO.
" lower button (5) and select the SECOND CODE NO.
" button (6) once and the present settings are SET.
" button (7) to return to the NORMAL MODE.
3
" button for a minimum of four seconds, and the
" button (2).
" button (3) and select the INDOOR UNIT NO to be set. (This
SiBE26-701
Field Setting

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents